Transformer full-load current

Three-phase current chart at 208, 240, and 480 V, plus a custom single- or three-phase calculation.

Three-phase transformer full-load current

Amps = kVA × 1,000 ÷ (√3 × volts)

√3 ≈ 1.732 · Voltages are line-to-line · Current rounded to the nearest whole amp

Full-load line current in amperes (A)
Transformer kVA208 V240 V480 V
30837236
401119648
6016714472
7520818090
112.5312271135
150416361180
225625541271
300833722361
5001,3881,203601
7502,0821,804902

Uses √3 at full precision. These are calculated full-load currents, not breaker ratings or conductor sizes. Protection and conductor selection require separate review.

Calculate a custom rating

Result

Enter your values and select Calculate to see a step-by-step result.

Reference2023 NEC Article 450; kVA current arithmetic

Full-load current only. Overcurrent protection and conductor selection have separate code requirements.